Compact air differential pressure transmitter
Metal body with hose barbs for dry air and gas, 0 to 0.5 kPa up to 0 to 1 bar, 4 to 20 mA or 0 to 5 V.
- Range
- 0 to 0.5 kPa up to 0 to 1 bar
- Accuracy
- ±0.5 % or ±1 % of span
- Output
- 4 to 20 mA or 0 to 5 V
- Protection
- IP65
- Built to the order code you configure
- Datasheet and dimension drawing with the quote
- Other ranges and connections quoted on request
PDT20 is a compact differential pressure transmitter for dry air and gas. The metal body is 60 by 27.5 mm, with two hose barbs on M10 x 1.5 threads marked high and low, and a cable outlet on the opposite end. It sits flat on a base flange with two 4 mm mounting holes, so it fits inside an air handling unit or a control panel.
In HVAC and buildings it reads filter loss, duct and fan pressure, indoor to outdoor differential and the pressurisation of lift lobbies and stairwells. It also reads draught on boilers whose furnace runs below atmospheric pressure. The medium has to be dry gas; mildly corrosive gas is within its limits, liquids are not.
Ranges run from 0 to 0.5 kPa up to 0 to 1 bar. Output is 4 to 20 mA on two wires or 0 to 5 V on three, from a 12 to 30 V DC supply. Accuracy is ±0.5 % or ±1 % of span, overload 1.5 x range, burst 2 x range, and the body is IP65.
Typical points
- Filter and strainer condition
- Duct, room and cleanroom pressure
- Pump differential pressure
- Flow across an orifice plate or flow element
Measurement
| Pressure type | Differential |
|---|---|
| Ranges | 0 to 0.5 kPa up to 0 to 1 bar |
| Accuracy | ±0.5 % or ±1 % of span |
| Overload | 1.5 x range |
| Burst pressure | 2 x range |
| Compensated temperature | -10 to 70 °C |
Medium and environment
| Medium | Dry air and gases, mildly corrosive at most |
|---|---|
| Operating temperature | -10 to 80 °C |
| Protection | IP65 |
Electrical
| Output | 4 to 20 mA two-wire, or 0 to 5 V three-wire |
|---|---|
| Supply | 12 to 30 V DC |
| Load, current output | Below (supply voltage - 9 V) / 20 mA |
| Load, voltage output | Above 100 kΩ |
| Electrical connection | Cable outlet with cable gland |
Mechanical
| Pressure ports | Two hose barbs on M10 x 1.5 threads, marked H and L |
|---|---|
| Fitting material | Aluminium alloy |
| Dimensions | 60 x 27.5 mm body, 102.5 mm long over the hose barbs |
| Mounting | Base flange with two 4 mm holes |
Common configurations. Any combination from the ordering code can be quoted.
| Range | Output | Accuracy | Pressure ports | Protection | Order code |
|---|---|---|---|---|---|
| 0 to 0.5 kPa | 4 to 20 mA | ±1 % of span | Hose barbs | IP65 | PDT20-P500-I-A1 |
| 0 to 0.5 kPa | 0 to 5 V | ±1 % of span | Hose barbs | IP65 | PDT20-P500-V5-A1 |
| 0 to 1 bar | 4 to 20 mA | ±0.5 % of span | Hose barbs | IP65 | PDT20-001-I-A05 |
| 0 to 1 bar | 0 to 5 V | ±0.5 % of span | Hose barbs | IP65 | PDT20-001-V5-A05 |
| 0 to 1 bar | 4 to 20 mA | ±1 % of span | Hose barbs | IP65 | PDT20-001-I-A1 |
One code from each group, in this order. Example: PDT20-P500-I-A05.
Range
| P500 | 0 to 0.5 kPa |
|---|---|
| 001 | 0 to 1 bar |
| X | Other range, state in the request |
Output
| I | 4 to 20 mA, two-wire |
|---|---|
| V5 | 0 to 5 V, three-wire |
Accuracy
| A05 | ±0.5 % of span |
|---|---|
| A1 | ±1 % of span |
- DatasheetPDF
- Dimension drawingSent with the quote
- Calibration certificate, per unit on requestSent with the quote
Questions about PDT20
Something else? Ask us about this model
Which range should I order for a filter or a room?
Choose a range just above the largest differential you expect, for example the dirty filter alarm point. Ranges run from 0 to 0.5 kPa up to 0 to 1 bar. State the range in the request and it becomes a line on the quote.
Can it measure water or other liquids?
No. The medium has to be dry air or gas, mildly corrosive at most. State the medium in the request and the quote names the model that suits it.