Bidirectional micro differential transmitter
Wall box for room and duct pressure from ±0.5 to ±10 kPa, analog output with optional RS485 and LCD.
- Range
- ±0.5 kPa up to ±10 kPa
- Accuracy
- ±1 % of span
- Output
- 4 to 20 mA, 0 to 10 V, RS485
- Resolution
- 0.1 Pa below 1 kPa
- Built to the order code you configure
- Datasheet and dimension drawing with the quote
- Other ranges and connections quoted on request
PDT21 is a micro differential pressure transmitter in a 100 x 70 x 47.5 mm wall box. It reads both sides of zero, from -0.5 to 0.5 kPa up to -10 to 10 kPa, so a room that swings between positive and negative stays on scale. Resolution is 0.1 Pa on ranges below 1 kPa and 1 Pa above, and response time is 0.5 s or less.
It is an HVAC and buildings instrument: room to corridor and indoor to outdoor differential, supply and extract duct pressure, and the pressurisation of lift lobbies and stairwells. The medium is dry air or gas. Two hose barbs, marked plus and minus, sit 16 mm apart on the bottom face next to the cable gland.
Output is 4 to 20 mA on two wires, or 4 to 20 mA, 0 to 5 V or 0 to 10 V on three. The four-wire version adds RS485 alongside the analog signal, for a building management bus. The front carries an LCD with three keys, or stays blind where nobody reads it on site. Supply is 12 to 30 V DC and accuracy is ±1 % of span.
Typical points
- Filter and strainer condition
- Duct, room and cleanroom pressure
- Pump differential pressure
- Flow across an orifice plate or flow element
Measurement
| Pressure type | Differential, both directions |
|---|---|
| Ranges | -0.5 to 0.5 kPa up to -10 to 10 kPa |
| Accuracy | ±1 % of span |
| Resolution | 0.1 Pa on ranges below 1 kPa, 1 Pa from 1 kPa |
| Response time | 0.5 s or less |
Medium and environment
| Medium | Dry air and gases |
|---|---|
| Operating temperature | -20 to 70 °C |
Electrical
| Output, two-wire | 4 to 20 mA |
|---|---|
| Output, three-wire | 4 to 20 mA, 0 to 5 V or 0 to 10 V |
| Output, four-wire | RS485 plus 4 to 20 mA, 0 to 5 V or 0 to 10 V |
| Supply | 12 to 30 V DC |
| Electrical connection | Cable gland to internal screw terminals |
Display and switching
| Display | LCD with three keys, or blind cover |
|---|
Mechanical
| Pressure ports | Two hose barbs, marked + and -, 16 mm apart |
|---|---|
| Housing | 100 x 70 x 47.5 mm wall box with two mounting lugs |
Common configurations. Any combination from the ordering code can be quoted.
| Range | Analog output | RS485 | Display | Order code |
|---|---|---|---|---|
| -0.5 to 0.5 kPa | 4 to 20 mA, two-wire | No | LCD | PDT21-P500-I-N-D |
| -0.5 to 0.5 kPa | 0 to 10 V | No | LCD | PDT21-P500-V10-N-D |
| -10 to 10 kPa | 4 to 20 mA | Yes | LCD | PDT21-K10-I-RS-D |
| -10 to 10 kPa | 0 to 5 V | No | Blind | PDT21-K10-V5-N-B |
| -10 to 10 kPa | 4 to 20 mA, two-wire | No | Blind | PDT21-K10-I-N-B |
One code from each group, in this order. Example: PDT21-P500-I-N-D.
Range
| P500 | -0.5 to 0.5 kPa |
|---|---|
| K10 | -10 to 10 kPa |
| X | Other range, state in the request |
Analog output
| I | 4 to 20 mA |
|---|---|
| V5 | 0 to 5 V |
| V10 | 0 to 10 V |
RS485 output
| N | None |
|---|---|
| RS | RS485, four-wire version |
Display
| D | LCD with three keys |
|---|---|
| B | Blind cover, no display |
- DatasheetPDF
- Dimension drawingSent with the quote
- Calibration certificate, per unit on requestSent with the quote
Questions about PDT21
Something else? Ask us about this model
Why a range on both sides of zero?
Rooms, lobbies and stairwells can swing either side of their reference as doors open and fans change speed. A range such as -0.5 to 0.5 kPa keeps both directions on one signal.
Can I have a range between the two listed?
Yes. Ranges run from -0.5 to 0.5 kPa up to -10 to 10 kPa. State the range in the request and it becomes a line on the quote.
Is it suitable for water or other liquids?
No. It is built for dry air and gas.