304 stainless submersible level transmitter
Hydrostatic probe for wells, tanks and wet wells, 1 to 50 m, with current, voltage or RS485 output.
- Depth range
- 0 to 1 m up to 0 to 50 m
- Output
- 4 to 20 mA, voltage or RS485
- Accuracy
- ±0.5 or ±1 % of span
- Probe
- 304 stainless, 28 mm, IP68
- Built to the order code you configure
- Datasheet and dimension drawing with the quote
- Other ranges and connections quoted on request
LT10 is a hydrostatic level transmitter that hangs on its cable in the liquid and reports depth from the pressure of the column above it. The probe is 304 stainless steel, 28 mm in diameter and 125 mm long, with a diffused silicon sensing element and a cable outlet sealed to IP68. Ranges run from 0 to 1 m up to 0 to 50 m of water.
It goes on boreholes, storage tanks, reservoirs and the wet wells of sewage pump stations, where the level drives pump start and stop or a high level alarm. In buildings it reads break tanks and storage tanks feeding constant pressure booster sets. Water, gasoline and diesel are listed media, so generator fuel tanks are in scope as well.
Output is chosen in the order code: 4 to 20 mA on two wires, 0 to 5 V or 0 to 10 V on three wires, or RS485 on four. Accuracy is ±0.5 % or ±1 % of span, medium temperature -10 to 70 °C with no freezing, and long-term stability ±0.1 % of span per year.
Typical points
- Borehole and well level
- Storage tank and reservoir level
- Wastewater wet well level for pump control
- River, canal and channel level
Used in
Measurement
| Measurement | Hydrostatic level, submersible |
|---|---|
| Depth range | 0 to 1 m up to 0 to 50 m water column |
| Accuracy | ±0.5 % or ±1 % of span |
| Long-term stability | ±0.1 % of span per year |
| Sensing element | Diffused silicon |
Medium and environment
| Media | Water, gasoline, diesel |
|---|---|
| Medium compatibility | Liquids compatible with 304 stainless steel |
| Medium temperature | -10 to 70 °C, no freezing |
| Storage temperature | -40 to 125 °C |
Electrical
| Output | 4 to 20 mA, 0 to 5 V, 0 to 10 V or RS485 |
|---|---|
| Supply, 4 to 20 mA | 9 to 30 V DC, two-wire |
| Supply, 0 to 5 V | 9 to 30 V DC, three-wire |
| Supply, 0 to 10 V | 15 to 30 V DC, three-wire |
| Supply, RS485 | 9 to 30 V DC, four-wire |
| Electrical connection | Cable outlet |
| Protection | IP68 |
Mechanical
| Probe material | 304 stainless steel |
|---|---|
| Probe size | 28 mm diameter, 125 mm long |
| Mounting | Suspended on its cable, no process thread |
Common configurations. Any combination from the ordering code can be quoted.
| Depth range | Output | Accuracy | Order code |
|---|---|---|---|
| 0 to 5 m | 4 to 20 mA | ±0.5 % of span | LT10-W5-I-A05 |
| 0 to 10 m | 4 to 20 mA | ±0.5 % of span | LT10-W10-I-A05 |
| 0 to 20 m | 4 to 20 mA | ±0.5 % of span | LT10-W20-I-A05 |
| 0 to 50 m | 4 to 20 mA | ±0.5 % of span | LT10-W50-I-A05 |
| 0 to 10 m | 0 to 10 V | ±0.5 % of span | LT10-W10-V10-A05 |
| 0 to 10 m | RS485 | ±0.5 % of span | LT10-W10-M-A05 |
| 0 to 5 m | 0 to 5 V | ±1 % of span | LT10-W5-V5-A1 |
One code from each group, in this order. Example: LT10-W1-I-A05.
Depth range
| W1 | 0 to 1 m water column |
|---|---|
| W2 | 0 to 2 m water column |
| W5 | 0 to 5 m water column |
| W10 | 0 to 10 m water column |
| W20 | 0 to 20 m water column |
| W30 | 0 to 30 m water column |
| W50 | 0 to 50 m water column |
| X | Other range, state in the request |
Output
| I | 4 to 20 mA, two-wire, 9 to 30 V DC |
|---|---|
| V5 | 0 to 5 V, three-wire, 9 to 30 V DC |
| V10 | 0 to 10 V, three-wire, 15 to 30 V DC |
| M | RS485, four-wire, 9 to 30 V DC |
Accuracy
| A05 | ±0.5 % of span |
|---|---|
| A1 | ±1 % of span |
- DatasheetPDF
- Dimension drawingSent with the quote
- Calibration certificate, per unit on requestSent with the quote
Questions about LT10
Something else? Ask us about this model
Which range should I order?
Choose a range whose top is above the highest liquid level over the probe. Any top from 1 m to 50 m of water can be built; state it in the request and it becomes a line on the quote.
Can it measure diesel or gasoline?
Yes. Water, gasoline and diesel are listed media, along with other liquids compatible with 304 stainless steel. For liquids that attack 304, LT11 in 316L or LT12 in PTFE is the better fit.
What cable length comes with it?
The length you order. State the distance from the probe to the junction box or panel in the request and it becomes a line on the quote.
Other submersible level transmitters
See all 9-
LT11316L stainless submersible level transmitter
0 to 1 m up to 0 to 50 m · 4 to 20 mA, voltage or RS485 -
LT12PTFE level transmitter for corrosive liquids
0 to 1 m up to 0 to 30 m · 4 to 20 mA, two-wire -
LT20Low-power level probe with voltage output
0 to 1 m up to 0 to 50 m · Low-voltage or ratiometric -
LT21Low-power digital level probe, RS485 or I2C
0 to 1 m up to 0 to 50 m -
LT22Low-power level and temperature probe, RS485
0 to 1 m up to 0 to 50 m -
LT40Wireless level probe with separate terminal
0 to 1 m up to 0 to 50 m · NB-IoT, LTE-M, 4G or LoRaWAN -
LT41Cellular or LoRaWAN level transmitter to 60 m
NB-IoT, 4G or LoRaWAN -
LT42LoRaWAN battery level gauge with display
0 to 1 m up to 0 to 50 m · LoRaWAN