316L stainless submersible level transmitter
Gauge or sealed level probe for 316L-compatible liquids, 1 to 50 m, with current, voltage or RS485 output.
- Depth range
- 0 to 1 m up to 0 to 50 m
- Output
- 4 to 20 mA, voltage or RS485
- Accuracy
- ±0.5 or ±1 % of span
- Probe
- 316L stainless, 28 mm, IP68
- Built to the order code you configure
- Datasheet and dimension drawing with the quote
- Other ranges and connections quoted on request
LT11 is a submersible hydrostatic level transmitter for liquids compatible with 316L stainless steel. It is built as gauge or sealed gauge, on a probe 28 mm in diameter and 125 mm long with a diffused silicon sensing element and an IP68 cable outlet. Ranges run from 0 to 1 m up to 0 to 50 m, with standard steps at 1, 2, 3, 5, 10, 20 and 30 m.
It goes on boreholes, reservoirs, treated water and wastewater tanks, and the wet wells where the level drives pump control. In buildings it reads break tanks and storage tanks feeding constant pressure booster sets. Where a liquid is too aggressive for 304 stainless steel but does not call for a plastic probe, 316L is the step between LT10 and LT12.
Output is 4 to 20 mA on two wires, 0 to 5 V or 0 to 10 V on three wires, or RS485 on four. Accuracy is ±0.5 % or ±1 % of span. Zero and span drift are each ±0.02 % of span per °C, overload is 2 x range, and medium temperature is -10 to 70 °C with no freezing.
Typical points
- Borehole and well level
- Storage tank and reservoir level
- Wastewater wet well level for pump control
- River, canal and channel level
Used in
Measurement
| Measurement | Hydrostatic level, submersible |
|---|---|
| Pressure type | Gauge or sealed gauge |
| Depth range | 0 to 1 m up to 0 to 50 m water column |
| Standard ranges | 1, 2, 3, 5, 10, 20, 30 m |
| Accuracy | ±0.5 % or ±1 % of span |
| Overload | 2 x range |
| Zero drift | ±0.02 % of span per °C |
| Span drift | ±0.02 % of span per °C |
| Long-term stability | ±0.5 % of span per year |
| Sensing element | Diffused silicon |
Medium and environment
| Medium compatibility | Liquids compatible with 316L stainless steel |
|---|---|
| Medium temperature | -10 to 70 °C, no freezing |
| Storage temperature | -20 to 100 °C |
Electrical
| Output | 4 to 20 mA, 0 to 5 V, 0 to 10 V or RS485 |
|---|---|
| Supply, 4 to 20 mA | 9 to 30 V DC, two-wire |
| Supply, 0 to 5 V | 9 to 30 V DC, three-wire |
| Supply, 0 to 10 V | 15 to 30 V DC, three-wire |
| Supply, RS485 | 9 to 30 V DC, four-wire |
| Electrical connection | Cable outlet |
| Protection | IP68 |
Mechanical
| Probe size | 28 mm diameter, 125 mm long |
|---|---|
| Mounting | Suspended on its cable, no process thread |
Common configurations. Any combination from the ordering code can be quoted.
| Depth range | Output | Accuracy | Order code |
|---|---|---|---|
| 0 to 3 m | 4 to 20 mA | ±0.5 % of span | LT11-W3-I-A05 |
| 0 to 5 m | 4 to 20 mA | ±0.5 % of span | LT11-W5-I-A05 |
| 0 to 10 m | 4 to 20 mA | ±0.5 % of span | LT11-W10-I-A05 |
| 0 to 30 m | 4 to 20 mA | ±0.5 % of span | LT11-W30-I-A05 |
| 0 to 10 m | RS485 | ±0.5 % of span | LT11-W10-M-A05 |
| 0 to 5 m | 0 to 10 V | ±1 % of span | LT11-W5-V10-A1 |
One code from each group, in this order. Example: LT11-W1-I-A05.
Depth range
| W1 | 0 to 1 m water column |
|---|---|
| W2 | 0 to 2 m water column |
| W3 | 0 to 3 m water column |
| W5 | 0 to 5 m water column |
| W10 | 0 to 10 m water column |
| W20 | 0 to 20 m water column |
| W30 | 0 to 30 m water column |
| W50 | 0 to 50 m water column |
| X | Other range, state in the request |
Output
| I | 4 to 20 mA, two-wire, 9 to 30 V DC |
|---|---|
| V5 | 0 to 5 V, three-wire, 9 to 30 V DC |
| V10 | 0 to 10 V, three-wire, 15 to 30 V DC |
| M | RS485, four-wire, 9 to 30 V DC |
Accuracy
| A05 | ±0.5 % of span |
|---|---|
| A1 | ±1 % of span |
- DatasheetPDF
- Dimension drawingSent with the quote
- Calibration certificate, per unit on requestSent with the quote
Questions about LT11
Something else? Ask us about this model
How does it differ from LT10?
LT11 is for liquids compatible with 316L stainless steel, LT10 for liquids compatible with 304. Probe size, depth ranges and output options are the same, and LT11 is offered as gauge or sealed gauge.
Gauge or sealed gauge?
Both are built. State which one in the request together with the depth range, and it becomes a line on the quote.
What cable length comes with it?
The length you order. State the distance from the probe to the junction box or panel in the request and it becomes a line on the quote.
Other submersible level transmitters
See all 9-
LT10304 stainless submersible level transmitter
0 to 1 m up to 0 to 50 m · 4 to 20 mA, voltage or RS485 -
LT12PTFE level transmitter for corrosive liquids
0 to 1 m up to 0 to 30 m · 4 to 20 mA, two-wire -
LT20Low-power level probe with voltage output
0 to 1 m up to 0 to 50 m · Low-voltage or ratiometric -
LT21Low-power digital level probe, RS485 or I2C
0 to 1 m up to 0 to 50 m -
LT22Low-power level and temperature probe, RS485
0 to 1 m up to 0 to 50 m -
LT40Wireless level probe with separate terminal
0 to 1 m up to 0 to 50 m · NB-IoT, LTE-M, 4G or LoRaWAN -
LT41Cellular or LoRaWAN level transmitter to 60 m
NB-IoT, 4G or LoRaWAN -
LT42LoRaWAN battery level gauge with display
0 to 1 m up to 0 to 50 m · LoRaWAN