Precision transmitter, ±0.1 % of span
±0.1 % of span and ±0.1 % per year stability from vacuum to 600 bar, for test benches and control loops.
- Range
- 0 to 0.4 up to 0 to 600 bar
- Accuracy
- ±0.1 % of span
- Output
- 4 to 20 mA or voltage
- Stability
- ±0.1 % of span per year
- Built to the order code you configure
- Datasheet and dimension drawing with the quote
- Other ranges and connections quoted on request
PT16 is the precision grade of the welded stainless range: ±0.1 % of span accuracy and ±0.1 % of span per year stability. The pressure chamber is 304 stainless steel, laser welded, and the electronics are temperature compensated from -20 to 85 °C, with zero and span drift of ±0.02 % of span per °C.
Ranges cover vacuum from -1 to 0 bar and 0 to 0.4 bar up to 0 to 600 bar gauge. It suits test benches, pump and valve test rigs, and points in water and HVAC plant where the reading feeds a control loop and a tight figure matters. Overpressure is 2 x range and burst pressure 3 x range.
Outputs are 4 to 20 mA two-wire, or 0 to 5 V, 0 to 10 V or 0.5 to 4.5 V three-wire, with surge and reverse polarity protection. For a local reading, it is available with a DIN 43650 form A connector that carries a display. Other connections include M12, Packard, AMP, Deutsch DT04 and cable outlets, IP65.
Typical points
- Pump discharge and suction pressure
- Hydraulic system pressure on machines
- Compressed air headers
- Chilled and heating water circuits
Measurement
| Pressure type | Gauge |
|---|---|
| Ranges | -1 to 0 bar, and 0 to 0.4 bar up to 0 to 600 bar |
| Accuracy | ±0.1 % of span |
| Long-term stability | ±0.1 % of span per year |
| Overpressure | 2 x range |
| Burst pressure | 3 x range |
| Zero temperature drift | ±0.02 % of span per °C |
| Span temperature drift | ±0.02 % of span per °C |
| Compensated temperature | -20 to 85 °C |
Medium and environment
| Medium temperature | -40 to 85 °C |
|---|---|
| Storage temperature | -40 to 125 °C |
| Shock | 100 g (11 ms) |
| Material | 304 stainless steel, laser welded |
Electrical
| Output | 4 to 20 mA two-wire; 0 to 5 V, 0 to 10 V or 0.5 to 4.5 V three-wire |
|---|---|
| Supply | 9 to 30 V DC (4 to 20 mA, 0 to 5 V); 15 to 30 V DC (0 to 10 V); 5 V DC (0.5 to 4.5 V) |
| Protection circuits | Surge and reverse polarity protection |
| Electrical connection | DIN 43650 form A (with or without display) or form C, M12, Packard, circular connector, AMP, Deutsch DT04-3P or DT04-4P, cable outlet or watertight cable outlet |
| Protection | IP65 |
Display and switching
| Local display | Optional, built into the DIN 43650 form A connector |
|---|
Mechanical
| Process connection | G1/8, G1/4, G3/8, G1/2, 1/8 NPT, 1/4 NPT, 3/8 NPT, 1/2 NPT, R1/8, R1/4, R3/8, R1/2, M12 x 1.5, M18 x 1.5, M20 x 1.5 |
|---|---|
| Body diameter | 22 mm |
| Wrench size | 22 mm |
Common configurations. Any combination from the ordering code can be quoted.
| Range | Process connection | Output | Electrical connection | Order code |
|---|---|---|---|---|
| -1 to 0 bar | G1/4 male | 0 to 5 V | Packard | PT16-V00-B2-V5-P |
| 0 to 1 bar | G1/4 male | 4 to 20 mA | DIN 43650 form A | PT16-001-B2-I-D |
| 0 to 10 bar | G1/4 male | 4 to 20 mA | DIN 43650 form A with display | PT16-010-B2-I-DD |
| 0 to 25 bar | G1/2 male | 4 to 20 mA | M12 | PT16-025-B4-I-M |
| 0 to 100 bar | M20 x 1.5 male | 0 to 10 V | M12 | PT16-100-M20-V10-M |
| 0 to 250 bar | 1/4 NPT male | 4 to 20 mA | Cable outlet | PT16-250-N2-I-C |
One code from each group, in this order. Example: PT16-V00-B1-I-D.
Range
| V00 | -1 to 0 bar |
|---|---|
| K40 | 0 to 40 kPa |
| 001 | 0 to 1 bar |
| 004 | 0 to 4 bar |
| 010 | 0 to 10 bar |
| 016 | 0 to 16 bar |
| 025 | 0 to 25 bar |
| 060 | 0 to 60 bar |
| 100 | 0 to 100 bar |
| 250 | 0 to 250 bar |
| 600 | 0 to 600 bar |
| X | Other range, state in the request |
Process connection
| B1 | G1/8 male |
|---|---|
| B2 | G1/4 male |
| B3 | G3/8 male |
| B4 | G1/2 male |
| N1 | 1/8 NPT male |
| N2 | 1/4 NPT male |
| N4 | 1/2 NPT male |
| R2 | R1/4 male |
| R4 | R1/2 male |
| M12 | M12 x 1.5 male |
| M18 | M18 x 1.5 male |
| M20 | M20 x 1.5 male |
Output
| I | 4 to 20 mA, two-wire |
|---|---|
| V5 | 0 to 5 V, three-wire |
| V10 | 0 to 10 V, three-wire |
| H | 0.5 to 4.5 V, three-wire, 5 V DC supply |
Electrical connection
| D | DIN 43650 form A connector |
|---|---|
| DD | DIN 43650 form A connector with display |
| DC | DIN 43650 form C connector |
| P | Packard connector |
| M | M12 connector, four-pin |
| A | Circular connector |
| C | Cable outlet |
| CW | Watertight cable outlet |
| AM | AMP connector, two-pin |
| T3 | Deutsch DT04-3P connector |
| T4 | Deutsch DT04-4P connector |
- DatasheetPDF
- Dimension drawingSent with the quote
- Calibration certificate, per unit on requestSent with the quote
Questions about PT16
Something else? Ask us about this model
How does PT16 differ from PT11?
Both use a laser-welded 304 stainless steel pressure chamber. PT16 is ±0.1 % of span with 2 x range overpressure and 3 x range burst pressure. PT11 is ±0.5 % of span with 1.5 x and 2 x, and adds absolute ranges.
Can PT16 show the pressure on site?
Yes. Choose the DIN 43650 form A connector with display, code DD in the electrical connection field.
Is a calibration certificate available?
Yes, one per unit on request. State it in the request and it becomes a line on the quote.
Other pressure transmitters
See all 31-
PT10Millivolt pressure sensor, glass-fused cell
0 to 6 up to 0 to 600 bar · 10 to 15 mV/V, four-wire -
PT11Wide-range welded stainless transmitter
0 to 0.2 up to 0 to 600 bar · 4 to 20 mA or voltage -
PT12Glass-fused pressure transmitter, 0.3 % grade
0 to 6 up to 0 to 600 bar · 4 to 20 mA or voltage -
PT13Glass-fused transmitter, 0.5 % grade
0 to 6 up to 0 to 600 bar · Gauge, sealed gauge, absolute -
PT14Low-range millivolt pressure sensor
0 to 0.4 up to 0 to 70 bar · 10 mV/V, four-wire -
PT15Low-pressure transmitter, vacuum to 6 bar
-1 bar up to 6 bar · 4 to 20 mA or voltage -
PT17Ceramic flat-diaphragm pressure transmitter
0 to 2 up to 0 to 25 bar · 4 to 20 mA, voltage or RS485 -
PT18Compact ceramic transmitter for water pumps
0 to 10, 16 or 25 bar · 4 to 20 mA or 0.5 to 4.5 V