Pressure transmitters

Strain gauge transmitter for refrigeration

Model PT30

Silicon strain gauge, 7/16-20 UNF female port, 0 to 50 kPa up to 0 to 60 bar, current or voltage output.

Range
0 to 50 kPa up to 0 to 60 bar
Accuracy
±0.5 % or ±1 % of span
Output
4 to 20 mA or 3 voltage outputs
Process port
7/16-20 UNF female

Configure PT30

Accuracy
Order code PT30-K50-I-P-A05

No payment now. The quote comes back with the price, the lead time and the documents.

  • Built to the order code you configure
  • Datasheet and dimension drawing with the quote
  • Other ranges and connections quoted on request

PT30 is a compact pressure transmitter for refrigeration, air conditioning and compressed air. The sensing element is a MEMS silicon strain gauge, glass-fused to the stainless steel body. From 6 bar up, the pressure chamber is machined from one piece of 17-4PH stainless steel, with no weld and no O-ring. Ranges below 6 bar use a 304 or 316 stainless steel body.

It goes on refrigeration and air conditioning circuits, on air compressors, and on the test stations of air conditioning production lines. That covers HVAC and buildings, compressor packages on the machinery side, and test benches. The process port is 7/16-20 UNF female, the thread used on refrigeration service connections.

Output is 4 to 20 mA two-wire, or 0.5 to 4.5 V, 0 to 5 V or 0 to 10 V three-wire, with a Packard, M12, or DIN 43650 form A or form C connector, all IP65. Accuracy is ±0.5 % or ±1 % of span. From 6 bar the transmitter takes 3 x range overload and 5 x range before burst.

Typical points

  • Pump discharge and suction pressure
  • Hydraulic system pressure on machines
  • Compressed air headers
  • Chilled and heating water circuits

Questions about PT30

Something else? Ask us about this model

Why do the overload figures change at 6 bar?

Ranges from 6 bar use the one-piece 17-4PH sensing body, rated 3 x range overload and 5 x range burst. Below 6 bar the body is 304 or 316 stainless steel, rated 1.5 x range overload and 3 x range burst.

What supply does each output need?

4 to 20 mA and 0 to 5 V run on 9 to 30 V DC, 0 to 10 V needs 15 to 30 V DC, and 0.5 to 4.5 V runs on 5 V DC.

Can it have a different process thread?

The standard port is 7/16-20 UNF female. State the thread you need in the request and it becomes a line on the quote.