Ceramic transmitter for refrigerant and oil
Ceramic cell rated for R134a and PAG oil up to 135 °C, female 7/16-20 UNF port, 0 to 10 up to 0 to 50 bar.
- Range
- 0 to 10 bar up to 0 to 50 bar
- Accuracy
- ±1 % of span
- Output
- 4 to 20 mA or 0.5 to 4.5 V
- Media
- R134a refrigerant, PAG oil
- Built to the order code you configure
- Datasheet and dimension drawing with the quote
- Other ranges and connections quoted on request
PT31 is a refrigerant pressure transmitter with a ceramic sensing element in a laser-welded 304 stainless steel body. It is rated for HFC-134a (R134a) refrigerant and PAG oil, with medium temperatures from -40 to 135 °C. Zero and span drift are each held to ±0.02 % of span per °C, and long-term stability to ±0.2 % of span per year.
It goes on air conditioning and refrigeration circuits, on air compressors, and on the inspection stations of air conditioning production lines, which places it in HVAC and buildings and on test benches. The female 7/16-20 UNF-2B port with a 16 mm hex is the refrigeration service thread, and the body is 23.4 mm across and 51.5 mm tall with the Packard connector.
Output is 4 to 20 mA two-wire on 9 to 30 V DC, or 0.5 to 4.5 V three-wire on 5 V DC, through a Packard, M12 or Yazaki connector, IP65. Ranges run from 0 to 10 bar up to 0 to 50 bar gauge, at ±1 % of span, with 2 x range overload and 3 x range burst.
Typical points
- Pump discharge and suction pressure
- Hydraulic system pressure on machines
- Compressed air headers
- Chilled and heating water circuits
Measurement
| Pressure type | Gauge |
|---|---|
| Ranges | 0 to 10 bar up to 0 to 50 bar |
| Accuracy | ±1 % of span |
| Long-term stability | ±0.2 % of span per year |
| Zero temperature drift | ±0.02 % of span per °C |
| Span temperature drift | ±0.02 % of span per °C |
| Overpressure | 2 x range |
| Burst pressure | 3 x range |
Medium and environment
| Media | HFC-134a (R134a) refrigerant, PAG oil |
|---|---|
| Medium temperature | -40 to 135 °C |
| Compensated temperature | -10 to 70 °C |
| Storage temperature | -40 to 150 °C |
| Shock | 100 g, 11 ms |
| Body material | 304 stainless steel, laser-welded |
Electrical
| Output | 4 to 20 mA two-wire, or 0.5 to 4.5 V three-wire |
|---|---|
| Supply | 9 to 30 V DC (4 to 20 mA); 5 V DC (0.5 to 4.5 V) |
| Electrical connection | Packard, M12 4-pin or Yazaki connector |
| Protection | IP65 |
| Circuit protection | Surge and reverse polarity protection |
Mechanical
| Process connection | 7/16-20 UNF-2B female, 16 mm hex |
|---|---|
| Sensing element | Ceramic |
| Dimensions | Ø23.4 mm body, 51.5 mm overall height with Packard connector |
Common configurations. Any combination from the ordering code can be quoted.
| Range | Output | Electrical connection | Protection | Order code |
|---|---|---|---|---|
| 0 to 10 bar | 0.5 to 4.5 V | Packard | IP65 | PT31-010-H-P |
| 0 to 25 bar | 0.5 to 4.5 V | Packard | IP65 | PT31-025-H-P |
| 0 to 40 bar | 0.5 to 4.5 V | Yazaki | IP65 | PT31-040-H-Y |
| 0 to 16 bar | 4 to 20 mA | M12 | IP65 | PT31-016-I-M |
| 0 to 25 bar | 4 to 20 mA | Packard | IP65 | PT31-025-I-P |
One code from each group, in this order. Example: PT31-010-I-P.
Range
| 010 | 0 to 10 bar |
|---|---|
| 016 | 0 to 16 bar |
| 025 | 0 to 25 bar |
| 040 | 0 to 40 bar |
| X | Other range, state in the request |
Output
| I | 4 to 20 mA, two-wire |
|---|---|
| H | 0.5 to 4.5 V, three-wire |
Electrical connection
| P | Packard connector |
|---|---|
| M | M12 connector, 4-pin |
| Y | Yazaki connector |
- DatasheetPDF
- Dimension drawingSent with the quote
- Calibration certificate, per unit on requestSent with the quote
Questions about PT31
Something else? Ask us about this model
Which media is it rated for?
HFC-134a (R134a) refrigerant and PAG oil, at medium temperatures from -40 to 135 °C. For another refrigerant, name it in the request and the quote states whether this model covers it.
Is the port male or female?
Female: a 7/16-20 UNF-2B internal thread with a 16 mm hex. For another thread, state it in the request and it becomes a line on the quote.
Can I order 0 to 50 bar?
Yes. Ranges run up to 0 to 50 bar. Choose X in the range field and state 0 to 50 bar in the request.
Other pressure transmitters
See all 31-
PT10Millivolt pressure sensor, glass-fused cell
0 to 6 up to 0 to 600 bar · 10 to 15 mV/V, four-wire -
PT11Wide-range welded stainless transmitter
0 to 0.2 up to 0 to 600 bar · 4 to 20 mA or voltage -
PT12Glass-fused pressure transmitter, 0.3 % grade
0 to 6 up to 0 to 600 bar · 4 to 20 mA or voltage -
PT13Glass-fused transmitter, 0.5 % grade
0 to 6 up to 0 to 600 bar · Gauge, sealed gauge, absolute -
PT14Low-range millivolt pressure sensor
0 to 0.4 up to 0 to 70 bar · 10 mV/V, four-wire -
PT15Low-pressure transmitter, vacuum to 6 bar
-1 bar up to 6 bar · 4 to 20 mA or voltage -
PT16Precision transmitter, ±0.1 % of span
0 to 0.4 up to 0 to 600 bar · 4 to 20 mA or voltage -
PT17Ceramic flat-diaphragm pressure transmitter
0 to 2 up to 0 to 25 bar · 4 to 20 mA, voltage or RS485